Its not as easy as it sounds. It can be done but there is no prepackaged
kit that I know of because how to do it depends on your system. Some
questions that have to be answered before you start a conversion: Are
you using a heating only baseboard/fancoil/radiant/etc? Is this
controlling a hot/cold water pipe change over system, or is it a 4 pipe
system? Are you controlling two completely different pieces of equipment
during cool/heat modes, are both those devices active the whole year or
is one off? What about separate fan controller (see bottom)? Is it
120volts or 240/208 volts? How many AMPs? You must know these answers
before you begin. Since I can't go over what to do in all situations I
will start with the basics.
There are two fundamental kinds of line voltage thermostats, switches
(the most common) and rheostats (or volt/amp variable controllers).
A switch type basically will open or close an electrical contact to
provide or disconnect power to the system. This is akin to a standard
light switch in your house, turn it on, you get electrical flow – hence
lights, off no light. The difference is that instead of flipping the
switch whenever you want to, a thermostat flips the switch based on what
the temperature is or it DIVERTS power between two possible paths.
A heater only line stat (thermostat) will only turn on when the temp
gets to cold (use this for baseboard, radiant heaters, etc) otherwise
its off ( a true light switch). But if you have a changeover system you
need one that sends (diverts) power between LESS than SETPOINT or MORE
than SETPOINT terminals (NC, NO). Often in this case a subbase is used
to switch the control type, so heating equipment can react to the
normally closed (NC) terminal and cooling to the normally open (NO) and
you can have a true OFF. This allows a line stat which diverts power
between NC and NO terminals have an off, but you should pair the subbase
with the stat per manufacturer’s instructions. A standard heat only
line stat will not send electricity down the NO terminal so it can never
tell a device to go on when it is hot (MORE than SETPOINT) and can't be
used with a heat/cool subbase or a changeover system. (Confused?, more
below to help you, read on!)
A thermostat is akin to a dimmer switch on your lights. It literally
changes the volts/amps delivered to the device based on switch position.
So more amps might mean more heat, turning the knob changes output
temperature, not overall room control. These are very rare and frankly
not very safe for home use, as a broken rheostat can start a fire in
your heating system. Some radiant floor heaters are like this. If you
have one of these do NOT attempt a 24volt conversion, it is too
complicated for you as evidenced by the fact that you searched for how
to do it. In fact I would recommend hiring a HVAC engineer to design
such a conversion, do not allow an HVAC contractor to figure it out
him/herself.
I will speak no more about this type and nothing below is
designed to help you with rheostat controls.
With the switch types there are two types of conversion, a voltage
converter/transformer or a voltage relay. I highly, highly, recommend a
relay. A relay is a switch that is controlled by a signal. In this case
you want the 24volt switch to turn on/off the 120/240 system.
BUT wait,
do you have a 24volt power supply???? Huh? In other words, where is the
power to send a signal on the 24volt system coming from? The relay won't
necessarily give you 24volt power, it merely reacts to 24volt line
changes. Some relays have a built in transformer, this is used to
provide 24volt power so you can use an unpowered thermostat. I recommend
these. An EXAMPLE is Honeywell Solid State Relay RT850 (don't just go
buy this without understanding your system). This provides 24volt power
regardless if the system is on or off. I see a lot of people
recommending a 24volt transformer only. I say this is bad.
Here is the
reason, a transformer takes all the power of the system, turns it to
24volts, sends it through the thermostat, which acts like a switch, and
then converts it back to 120/240 volts. Here are the many problems: One
the amps going through the 24volt system are way too high for most
thermostats to handle, two if the transformer stops working well it can
damage your thermostat or worse (like start a fire), three the ability
to switch on/off is heavily dependent on the nature of the transformer
itself and how it handles electricity, which is too complicated to go
into and four, it gets hot/very power wasteful.
If you go the way I don't recommend in theory all you need is the relay
and a thermostat with two wire control. Good luck, don't say I didn't
warn you.
If you go my way with the relay w/ built in transformer you have to see
if you have a subbase and what it does. Depending on what kind of
equipment you have to control will determine if you need to leave in the
subbase or take it out. With the heat/cool/off system I will usually
take it out, there are some odd cases where its best to leave it in.
But you might need TWO (2) relays if you control two totally different
pieces of equipment (one to heat, the other to cool and they are both
active all year) or have a 4 pipe system (a quick check -but not
sufficient enough to replace an investigation – to see if you need two
relays, you will have a whole bunch of wires coming/going to the
thermostat). In this case (needing two relays) you need to realize that
you will have 6, 24 volt terminals (three from each relay): the two 'C's
(common) get wired together, the heating system relay W is a true W
(white - heat) but the cooling system relay W is really a Y (yellow -
cool) and the two 'R's (reds) can be wired together so you end up with a
4 wire system (W,Y,R,C) and you need a 4 wire thermostat (easy to
find).
For a seasonal changeover system (think apartment building where during
one half the year you can only heat vs other half you can only cool) you
should only need one relay as all you’re doing is turning on the system
or turning it off. This config will work for a changeover system with
or without a subbase previously used.
{A changeover with no subbase means that during the winter when the Temp
setpoint is satisfied it actually TRIES to cool, but the cooling system
is disconnected somewhere else so it really turns off. During the
summer the opposite occurs. In a two pipe changeover system this doesn't
work because there is no off, during the summer after setpoint is
reached it would shift over and try to heat, but turning on heat is the
same as turning on cold (it opens a valve and turns on a fan, whether
hot or cold water flows through the valve is inconsequential to the
switch) so it would end up just staying on all the time, a total waste.
The subbase allows for OFF, in essence that's all it does. Hopefully
this clarifies what I said above. }
Then you just need a two or three wire thermostat.
If you have a fan, particularly a variable speed fan in the loop (like
the person asking the question seems to) it gets tricky. You will know
this because your thermostat gives you separate fan controls (like fan
high/low/off/auto). You need to realize what you are trying to do. You
need one controller that can turn off and on the heating/cooling system
at the right time and another that can turn on or off the fan at the
right time, AND for variable speed fans you need the relay to somehow
signal the right amount of power to send to the fan. PLUS the fan
controller needs to talk to the heating/cooling controller because you
want it to go on and off with the heat/cool system OR have a FAN ON
option. At a minimum to do this you need two relays and a thermostat
with a separate fan control capability (usually a G or green terminal) -
a higher end thermostat can do this.
Explaining how to get the variable
fan speed is too complicated for here. But understand the relay is
merely a switch it can't regulate how MUCH power the fan gets, you need
something that can change the amount of power to the fan. Honestly I
would just leave the fan power regulator as a separate line voltage
switch and allow the thermostat to turn on the fan and I would choose if
I want high or low fan power. Trying to do this with 24volt controls
requires an HVAC controls engineer. So in other words, get the 'two
relays with G terminal thermostat' and on the relay controlling the fan,
on the relay output (red 120/240 volt wire) have a fan high/low power
controller there and place the switch somewhere accessible.
Closing – always check the kinds of wires you have, the volts/amps etc.
Know what they all do. Practice safe electrical procedures. When in
doubt or if you are not comfortable performing this work, higher a
licensed electrician.
No comments:
Post a Comment
Note: Only a member of this blog may post a comment.